PRECISION DIGITAL CORPORATION 89 October Hill Road • Holliston MA 01746 USA Tel (800) 343-1001 • Fax (508) 655-8990 www.predig.com PD6300 Pulse Inpu
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 10 OVERVOLTAGE CATEGORY Installation Overvoltage Category II: Local level with smaller tra
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 11 DECIMAL POINT Up to five decimal places or none: d.ddddd, d.dddd, d.ddd, d.dd, d.d, or
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 12 TOTAL OVERFLOW OVERRIDE Program total reset for automatic with 0.1 second delay and set
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 13 RELAY RESET User selectable via front panel buttons, digital inputs, or PC 1. Automat
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 14 Modbus® RTU Serial Communications SLAVE ID 1 – 247 (Meter address) BAUD RATE 300 - 19,2
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 15 COMPLIANCE INFORMATION Safety UL & c-UL LISTED USA & Canada UL 508 Industrial C
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 16 Note: Testing was conducted on PD6300 meters installed through the cov-ers of grounded
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 17 INSTALLATION There is no need to remove the meter from its case to complete the install
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 18 Mounting Dimensions 1.76"(45 mm)0.59"(15 mm)4.77"(121 mm)2.45"(62 m
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 19 Configuration for 12 or 24 VDC Power Option Warning! Do not exceed voltage rating of t
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 2 Disclaimer The information contained in this document is subject to change without noti
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 20 Transmitter Supply Voltage Selection (P+, P-) All meters, including models equipped wit
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 21 Connectors Labeling The connectors’ label, affixed to the meter, shows the location of
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 22 Signal Connections Signal connections are made to a five-terminal connector labeled SI
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 23 S-P-21354P+ S+COMINPUT SIGNALV PNP NPNmVLEVEL TYPENPNSENSOR4.7 k-ohmInternal pull-up+5
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 24 Modbus RTU Serial Communications Serial communications connection is made to an RJ45 co
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 25 Switching Inductive Loads The use of suppressors (snubbers) is strongly recommended whe
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 26 4-20 mA Output Connections Connections for the 4-20 mA transmitter output are made to t
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 27 External Relay & Digital I/O Connections The relay and digital I/O expansion module
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 28 123456+5 I1 I2 I3 I4 O178O2 O3910O4 GDI 1-4 DO 1-45 VDC GND Figure 17: Digital I/O Mod
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 29 SETUP AND PROGRAMMING The meter has been factory calibrated to read input frequency
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 3 Table of Contents INTRODUCTION --------------------------------------------------------
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 30 Front Panel Buttons and Status LED Indicators Button Symbol Description LED Status
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 31 Display Functions and Messages The meter displays various functions and messages during
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 32 Display Parameter Action/Setting Description Assign Assignment Assign relays to rate, t
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 33 Display Parameter Action/Setting Description off Fail-safe off Disable fail-safe operat
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 34 Display Parameter Action/Setting Description T rst Total reset Program total reset mode
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 35 Main Menu The main menu consists of the most commonly used functions: Reset, Control, S
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 36 Setting Numeric Values The numeric values are set using the Right and Up arrow buttons.
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 37 Setting Up the Rate/Totalizer Meter (setup) The Setup menu is used to select: 1. Enabl
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 38 Setting the Input Signal (Input) There are two switches, located to the right of the in
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 39 Setting the Display Parameter & Intensity (dsplay) The main display (Big) can be pr
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 4 Reset Menu (reset) ------------------------------------------------------------ 36Contr
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 40 Display Setup Menu Dsplay setup big dsplay Little dsplay d-Inty dsplay Int 1 d-Inty I
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 41 Character Set for Engineering Units Display (d unit) The small display can be programme
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 42 Programming the Rate/Totalizer (prog) It is very important that one reads the following
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 43 K-Factor Calibration (Factor) The meter may be calibrated using the K-Factor function.
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 44 MeterView® Pro Software The meter can also be programmed using the PC-based MeterView P
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 45 Scaling the Meter (SCALE) The pulse inputs can be scaled to display the process variabl
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 46 Error Message (Error) An error message indicates that the calibration or scaling proces
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 47 Gate Settings Slow Pulse Rate Low Gate* (sec) High Gate (sec) Min Freq** (Hz) 1.0 2.0
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 48 Time Base, Total Conversion Factor & Total Reset The time base, total conversion f
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 49 Calibrating the Meter with External Source (Cal) To scale the meter without a signal so
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 5 Acknowledging Relays ------------------------------------------------------ 64Setting U
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 50 Setting the Relay Operation (relay) This menu is used to set up the operation of the re
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 51 Note: The setup of relays 2-8 follows the same pattern shown here for relay 1.
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 52 Setting the Relay Action Operation of the relays is programmed in the Action menu. The
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 53 Programming Set and Reset Points High alarm indication: program set point above reset p
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 54 Relay and Alarm Operation Diagrams The following graphs illustrate the operation of the
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 55 Low Alarm Operation (Set < Reset) ResetSetInputRelayLEDenergizedde-energizedonoffRel
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 56 High Alarm with Fail-Safe Operation (Set > Reset) RelayLEDInputAutomatic (non-latchi
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 57 Low Alarm with Fail-Safe Operation (Set < Reset) ResetSetInputRelayLEDAutomatic (non
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 58 Alternation Control Operation Pump 1Relay1 SetRelay2 ResetRelay2 SetRelay1 SetR
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 59 Rate Relay Sampling Operation SetResetRelayLEDInputSampleTimeSampleTimeSampleTime When
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 6 Table of Figures Figure 1: 1/8 DIN Panel Cutout and Mounting ...
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 60 Time Delay Operation The following graphs show the operation of the time delay functio
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 61 Relay Operation Details Overview The relay capabilities of the meter expand its usefuln
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 62 Front Panel LEDs The LEDs on the front panel provide status indication for the followin
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 63 Non-Latching Relay (Auto) Automatic reset only Condition LED RelayNormal Off Off Alarm
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 64 Latching Relay (Lt-Clr) Manual reset only after alarm condition has cleared Condition L
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 65 Setting Up the Interlock Relay Feature Relays 1-4 can be set up as interlock relays. To
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 66 Scaling the 4-20 mA Analog Output (Aout) The 4-20 mA analog output can be scaled to pro
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 67 Setting Up the Password (pass) The Password menu is used for programming three levels o
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 68 Total Reset Password & Non-Resettable Total The total and the grand total can be pa
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 69 Making Changes to a Password Protected Meter If the meter is password protected, the me
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 7 INTRODUCTION The PROVU® PD6300 is a multipurpose, easy to use pulse rate/totalizer ideal
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 70 Advanced Features Menu To simplify the setup process, functions not needed for most app
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 71 Advanced Features Menu & Display Messages The following table shows the functions a
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 72 Display Parameter Action/Setting O-rang Overrange Program mA output for display overra
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 73 Display Parameter Action/Setting Cutoff Cutoff Cutoff value T tb Total time base Set t
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 74 Modbus RTU Serial Communications (serial) The meter is equipped with serial communicati
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 75 Select Menu (SElEct) The Select menu is used to select the math function applied to the
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 76 Multi-Point Linearization (Linear) Meters are set up at the factory for linear function
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 77 Low-Flow Cutoff (CutofF) The low-flow cutoff feature allows the meter to be programmed
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 78 Programmable Function Keys User Menu (user) The User menu allows the user to assign the
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 79 Meter Copy Function (Copy) The Copy function is used to copy (or clone) all the setting
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 8 ORDERING INFORMATION Standard Models 85-265 VAC Model 12/24 VDC Model Options Installed
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 80 Meter Copy or Cloning Instructions ! Caution! Do not connect the two meters to the same
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 81 METER OPERATION The meter accepts pulses (e.g. ±40mV to ± 8V), square wave (0-5, 0-12V,
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 82 Maximum/Minimum Readings The max & min readings (peak & valley) reached by the
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 83 TROUBLESHOOTING The rugged design and the user-friendly interface of the meter should m
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 84 Reset Meter to Factory Defaults When the parameters have been changed in a way that is
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 85 Factory Defaults & User Settings The following table shows the factory setting for
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 86 Parameter Display Default Setting User Setting Relay 3 assignment Asign3 Rate Relay
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 87 Parameter Display Default Setting User Setting Source analog output Source Rate/proce
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 88 Troubleshooting Tips Symptom Check/Action No display at all Check power at power connec
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 89 Alphabetical List of Display Functions & Messages Display Parameter Action/Settin
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 9 SPECIFICATIONS Except where noted all specifications apply to operation at +25°C. Genera
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 90 Display Parameter Action/Setting Description Calib Calibrate Calibrate 4-20 mA output
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 91 Display Parameter Action/Setting Description DSet 1 Display set 1 Select to display s
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 92 Display Parameter Action/Setting Description LatCH Latching Set relay for latching ope
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 93 Display Parameter Action/Setting Description On 1 On Set relay 1 On time delay O-rang
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 94 Display Parameter Action/Setting Description Rst t Reset Total Reset total Sanmpl Samp
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual 95 NOTES
Model PD6300 Pulse Input Rate/Totalizer Instruction Manual LIM6300_D.doc SFT039 Ver 2.000 & up 08/10 How to Contact Precision Digital