PD6800-0L1 EXPLOSION-PROOF LOOP-
POWERED PROCESS METER WITH BAR GRAPH
4-20 mA Input Loop-Powered
Modern, Sleek and Practical Enclosure
Easy-to-Read 20-Segment Tank Level Indicator
5 Digits, 0.6" (15.2 mm) Upper Display
7 Alphanumeric Character, 0.4" (10.2 mm) Lower Display
SafeTouch
®
Through-Glass Button Programming
Password Protection
32-Point, Square Root, or Exponential Linearization
Open Collector Alarm Output
Loop-Powered or External DC-Powered Backlight Standard
HART
®
Protocol Transparent
3 V Drop (6.0 V with Backlight)
Explosion-Proof, IP68, NEMA 4X Enclosure
Operates from -40 to 75°C
Seitenansicht 0
1 2 3 4 5 6 ... 47 48

Inhaltsverzeichnis

Seite 1

PRECISION DIGITAL CORPORATION 89 October Hill Road • Holliston MA 01746 USA Tel (800) 343-1001 • Fax (508) 655-8990 www.predig.com PD6800-0L1 EXPLOS

Seite 2 - Disclaimer

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 10 INSTALLATION For Installation in USA: The PD6800-0L1 must be installed in accordance with

Seite 3 - ORDERING INFORMATION

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 11 Mounting The PD6800-0L1 has two slotted mounting flanges that may be used for pipe mounti

Seite 4 - Table of Contents

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 12 Connections (continued) SIGNAL + 4-20 mA signal input positive terminal connection SIGNA

Seite 5 - Table of Figures

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 13 Connections & Wiring Diagrams Signal connections are made to a four-terminal connecto

Seite 6 - SPECIFICATIONS

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 14 Figure 4. Connections with Externally-Powered Backlight It is possible to use the same

Seite 7 - Open Collector Output

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 15 Open Collector Output Connections Output connections are made to two terminals labeled OU

Seite 8

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 16 SETUP AND PROGRAMMING There is no need to recalibrate the meter for milliamps when first

Seite 9 - SAFETY INFORMATION

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 17 SafeTouch® Buttons The PD6800-0L1 is equipped with four sensors that operate as through-g

Seite 10 - INSTALLATION

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 18 Buttons and Display Button Symbol Description Symbol Status Menu Tank Level Indicat

Seite 11 - Connections

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 19 Menu Button  Press the Menu button to enter Programming Mode.  Press the Menu button du

Seite 12 - Connections (continued)

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 2 Disclaimer The information contained in this document is subject to change without notice.

Seite 13 - Transmitter

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 20 Main Menu The main menu consists of the most commonly used functions: Setup, Advanced, an

Seite 14 - OUTPUT RESET

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 21 Setting Up the Meter (SETUP) The Setup menu is used to select: 1. Engineering units deci

Seite 15 - Alarm Recorder

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 22 Setting Numeric Values The numeric values are set using the RIGHT and UP arrow buttons. P

Seite 16 - SETUP AND PROGRAMMING

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 23 Main Menu Display Functions & Messages The meter displays various functions and messa

Seite 17 - Buttons

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 24 Scaling the Meter (SCaLe) The 4-20 mA input can be scaled to display the process in engin

Seite 18 - Buttons and Display

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 25 Minimum Input Span The minimum input span is the minimum difference between input 1 and i

Seite 19

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 26 Configuring the Display (DISPLAY) The lower (BOTTOM) display may be configured to display

Seite 20 - Main Menu

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 27 Setting the TAG (TAG) Any bottom display setting that includes a tag will require the tag

Seite 21 - Setting Up the Meter (SETUP)

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 28 Setting Up the Password (PASSWRD) The Password menu is used to program a five-digit passw

Seite 22 - SETuP 1111.1 222.22

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 29 Disabling Password Protection To disable the password protection, access the Password men

Seite 23

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 3 INTRODUCTION The PD6800-0L1 is a rugged, explosion-proof loop-powered meter fully featured

Seite 24 - Scaling the Meter (SCaLe)

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 30 Advanced Features Menu (ADVANCE) To simplify the setup process, functions not needed for

Seite 25 - Minimum Input Span

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 31 Advanced Features Menu & Display Messages The following table shows the Advanced feat

Seite 26

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 32 Display Parameter Action/Setting ICAL Internal Calibration Enter internal reference cali

Seite 27 - Setting the TAG (TAG)

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 33 Alarm Output (OUTPUT) The PD6800-0L1 is equipped with an NPN open collector output that m

Seite 28 - Locking the Meter

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 34 Input Signal Filter (FILTER) The noise filter is available for unusually noisy signals th

Seite 29 - Did you forget the password?

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 35 Level Input Live Signal Calibration (LVL CAL) The meter can be calibrated using a current

Seite 30

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 36 Internal Calibration (ICAL) There is no need to recalibrate the meter when first receive

Seite 31

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 37 Level Input Multipoint Linearization (MULTIPT) This menu enables multipoint linearization

Seite 32

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 38 OPERATION Front Panel Buttons Operation Button Symbol Description Press to Enter or Exit

Seite 33 - Alarm Output (OUTPUT)

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 39 Display Maximum, Minimum, and Input Current The maximum and minimum values and the measur

Seite 34 - Input Signal Filter (FILTER)

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 4 Table of Contents INTRODUCTION -----------------------------------------------------------

Seite 35

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 40 Reset Meter to Factory Defaults When the parameters have been changed in a way that is di

Seite 36 - Internal Calibration (ICAL)

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 41 Factory Defaults & User Settings The following table shows the factory setting for mo

Seite 37 - Information (INFO)

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 42 TROUBLESHOOTING Due to the many features and functions of the meter, it’s possible that t

Seite 38 - OPERATION

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 43 MOUNTING DIMENSIONS All units: inches [mm] Figure 9. Enclosure Dimensions – Front View

Seite 39

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 44 Figure 10. Enclosure Dimensions – Side Cross Section View 3.35 [85.0]4.15 [105.5]3.22

Seite 40

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 45 QUICK USER INTERFACE REFERENCE SetupRunmA DisplayAdvanced FeaturesUP Arrow MENUMENUME

Seite 41

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 46

Seite 42 - TROUBLESHOOTING

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 47 EC DECLARATION OF CONFORMITY Issued in accordance with ATEX Directive 94/9/EC Manufact

Seite 43 - MOUNTING DIMENSIONS

PD6800-0L1 Loop-Powered Process Meter Instruction Manual LIM6800L_B SFT087 Ver 1.300 & up 04/15 How to Contact Precision Digital  For Tech

Seite 44 - 4.86 [123.5]

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 5 Internal Calibration (ICAL) ...

Seite 45 - Features

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 6 SPECIFICATIONS Except where noted all specifications apply to operation at +25°C. General

Seite 46

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 7 Input ACCURACY ±0.03% of calibrated span ±1 count, square root & programmable expo

Seite 47 - EC DECLARATION OF CONFORMITY

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 8 Product Ratings and Approvals FM Class I, Division 1, Groups B, C, D Class II, Division 1

Seite 48 - 04/15

PD6800-0L1 Loop-Powered Process Meter Instruction Manual 9 Electromagnetic Compatibility EMISSIONS EN 61326:2006 Safety requirements for measurement,