PRECISION DIGITAL CORPORATION 89 October Hill Road • Holliston MA 01746 USA Tel (800) 343-1001 • Fax (508) 655-8990 www.predig.com PD6800-0L1 EXPLOS
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 10 INSTALLATION For Installation in USA: The PD6800-0L1 must be installed in accordance with
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 11 Mounting The PD6800-0L1 has two slotted mounting flanges that may be used for pipe mounti
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 12 Connections (continued) SIGNAL + 4-20 mA signal input positive terminal connection SIGNA
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 13 Connections & Wiring Diagrams Signal connections are made to a four-terminal connecto
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 14 Figure 4. Connections with Externally-Powered Backlight It is possible to use the same
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 15 Open Collector Output Connections Output connections are made to two terminals labeled OU
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 16 SETUP AND PROGRAMMING There is no need to recalibrate the meter for milliamps when first
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 17 SafeTouch® Buttons The PD6800-0L1 is equipped with four sensors that operate as through-g
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 18 Buttons and Display Button Symbol Description Symbol Status Menu Tank Level Indicat
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 19 Menu Button Press the Menu button to enter Programming Mode. Press the Menu button du
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 2 Disclaimer The information contained in this document is subject to change without notice.
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 20 Main Menu The main menu consists of the most commonly used functions: Setup, Advanced, an
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 21 Setting Up the Meter (SETUP) The Setup menu is used to select: 1. Engineering units deci
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 22 Setting Numeric Values The numeric values are set using the RIGHT and UP arrow buttons. P
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 23 Main Menu Display Functions & Messages The meter displays various functions and messa
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 24 Scaling the Meter (SCaLe) The 4-20 mA input can be scaled to display the process in engin
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 25 Minimum Input Span The minimum input span is the minimum difference between input 1 and i
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 26 Configuring the Display (DISPLAY) The lower (BOTTOM) display may be configured to display
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 27 Setting the TAG (TAG) Any bottom display setting that includes a tag will require the tag
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 28 Setting Up the Password (PASSWRD) The Password menu is used to program a five-digit passw
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 29 Disabling Password Protection To disable the password protection, access the Password men
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 3 INTRODUCTION The PD6800-0L1 is a rugged, explosion-proof loop-powered meter fully featured
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 30 Advanced Features Menu (ADVANCE) To simplify the setup process, functions not needed for
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 31 Advanced Features Menu & Display Messages The following table shows the Advanced feat
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 32 Display Parameter Action/Setting ICAL Internal Calibration Enter internal reference cali
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 33 Alarm Output (OUTPUT) The PD6800-0L1 is equipped with an NPN open collector output that m
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 34 Input Signal Filter (FILTER) The noise filter is available for unusually noisy signals th
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 35 Level Input Live Signal Calibration (LVL CAL) The meter can be calibrated using a current
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 36 Internal Calibration (ICAL) There is no need to recalibrate the meter when first receive
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 37 Level Input Multipoint Linearization (MULTIPT) This menu enables multipoint linearization
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 38 OPERATION Front Panel Buttons Operation Button Symbol Description Press to Enter or Exit
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 39 Display Maximum, Minimum, and Input Current The maximum and minimum values and the measur
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 4 Table of Contents INTRODUCTION -----------------------------------------------------------
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 40 Reset Meter to Factory Defaults When the parameters have been changed in a way that is di
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 41 Factory Defaults & User Settings The following table shows the factory setting for mo
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 42 TROUBLESHOOTING Due to the many features and functions of the meter, it’s possible that t
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 43 MOUNTING DIMENSIONS All units: inches [mm] Figure 9. Enclosure Dimensions – Front View
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 44 Figure 10. Enclosure Dimensions – Side Cross Section View 3.35 [85.0]4.15 [105.5]3.22
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 45 QUICK USER INTERFACE REFERENCE SetupRunmA DisplayAdvanced FeaturesUP Arrow MENUMENUME
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 46
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 47 EC DECLARATION OF CONFORMITY Issued in accordance with ATEX Directive 94/9/EC Manufact
PD6800-0L1 Loop-Powered Process Meter Instruction Manual LIM6800L_B SFT087 Ver 1.300 & up 04/15 How to Contact Precision Digital For Tech
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 5 Internal Calibration (ICAL) ...
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 6 SPECIFICATIONS Except where noted all specifications apply to operation at +25°C. General
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 7 Input ACCURACY ±0.03% of calibrated span ±1 count, square root & programmable expo
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 8 Product Ratings and Approvals FM Class I, Division 1, Groups B, C, D Class II, Division 1
PD6800-0L1 Loop-Powered Process Meter Instruction Manual 9 Electromagnetic Compatibility EMISSIONS EN 61326:2006 Safety requirements for measurement,