PD6830 Pulse Input Rate/Totalizer Instruction Manual 10 OPTO-ISOLATED IN-PUT Sourcing pulse or square wave 0-5 V, 0-12 V, or 0-24 V; Logic High: 2-24
PD6830 Pulse Input Rate/Totalizer Instruction Manual LIM6830_K SFT050 Ver 3.200 & up 03/15 How to Contact Precision Digital For Technical Suppo
PD6830 Pulse Input Rate/Totalizer Instruction Manual 11 Rate/Totalizer DISPLAY ASSIGNMENT The Top display is assigned to rate or total. The Bottom d
PD6830 Pulse Input Rate/Totalizer Instruction Manual 12 TOTAL OVERFLOW AND ROLLOVER The total can display up to 9,999,999,999,999. Up to 9,999,999 can
PD6830 Pulse Input Rate/Totalizer Instruction Manual 13 4-20 mA Transmitter Output OUTPUT SOURCE Rate/process, total, grand total, or disabled SCALIN
PD6830 Pulse Input Rate/Totalizer Instruction Manual 14 PULSE OUTPUT K-FACTOR (COUNT) K-factor (couNT) programmable from 0.000001 to 9999999. Rate pul
PD6830 Pulse Input Rate/Totalizer Instruction Manual 15 Product Ratings and Approvals FM Class I, Division 1, Groups B, C, D Class II, Division 1,
PD6830 Pulse Input Rate/Totalizer Instruction Manual 16 Electromagnetic Compatibility EMISSIONS EN 61326:2006 Safety requirements for measurement, con
PD6830 Pulse Input Rate/Totalizer Instruction Manual 17 INSTALLATION For Installation in USA: The PD6830 must be installed in accordance with the Nati
PD6830 Pulse Input Rate/Totalizer Instruction Manual 18 Mounting The PD6830 has two slotted mounting flanges that may be used for pipe mounting or wal
PD6830 Pulse Input Rate/Totalizer Instruction Manual 19 Connections (continued) S+ Signal input positive terminal connection S- Signal input negativ
PD6830 Pulse Input Rate/Totalizer Instruction Manual 2 Disclaimer The information contained in this document is subject to change without notice. Prec
PD6830 Pulse Input Rate/Totalizer Instruction Manual 20 Input Signal Connections Signal connections are made to a barrier terminal mounted in the base
PD6830 Pulse Input Rate/Totalizer Instruction Manual 21 Figure 5. NPN Open Collector Input (NPN) Figure 6. PNP Sensor with External Power (PNP)
PD6830 Pulse Input Rate/Totalizer Instruction Manual 22 DC Power Connection Models configured for DC power (PD6830-A) are provided with a terminal lab
PD6830 Pulse Input Rate/Totalizer Instruction Manual 23 4-20 mA Transmitter Output Connections Output connections are made to two terminals labeled LP
PD6830 Pulse Input Rate/Totalizer Instruction Manual 24 Open Collector Output Connections Open collector output 1 and 2 connections are made to termin
PD6830 Pulse Input Rate/Totalizer Instruction Manual 25 Battery Replacement Battery-equipped models have a battery charge monitor. When the battery i
PD6830 Pulse Input Rate/Totalizer Instruction Manual 26 SETUP AND PROGRAMMING There is no need to recalibrate the meter for frequency in Hz when fir
PD6830 Pulse Input Rate/Totalizer Instruction Manual 27 SafeTouch® Button Tips and Troubleshooting The SafeTouch Buttons are designed to filter normal
PD6830 Pulse Input Rate/Totalizer Instruction Manual 28 Buttons and Display ENTERDISPLAYRESETMENU Button Symbol Description Symbol Status Menu/ Safe
PD6830 Pulse Input Rate/Totalizer Instruction Manual 29 Menu Button Hold the Menu SafeTouch® button when in power save mode (display will show ) to
PD6830 Pulse Input Rate/Totalizer Instruction Manual 3 INTRODUCTION The ProtEX-RTP PD6830 is a rugged, explosion-proof, pulse input rate/totalizer for
PD6830 Pulse Input Rate/Totalizer Instruction Manual 30 Setting Numeric Values The numeric values are set using the Right and Up arrow buttons. Press
PD6830 Pulse Input Rate/Totalizer Instruction Manual 31 Main Menu The main menu separates the most commonly used functions in the Setup menu, and mor
PD6830 Pulse Input Rate/Totalizer Instruction Manual 32 Setup Menu Display Functions & Messages The meter displays various functions and messages
PD6830 Pulse Input Rate/Totalizer Instruction Manual 33 Display Parameter Action/Setting P/HECtL Pulses/hectoliter Set K-factor in pulses per hectoli
PD6830 Pulse Input Rate/Totalizer Instruction Manual 34 Display Parameter Action/Setting CHAR Character Set a character in a custom unit label ratCF
PD6830 Pulse Input Rate/Totalizer Instruction Manual 35 Display Parameter Action/Setting TOTAL+U````````````````` Total & units Display total and
PD6830 Pulse Input Rate/Totalizer Instruction Manual 36 Setting Up the Meter (SETUP) The Setup menu is used to select: 1. Input type selection (INPuT
PD6830 Pulse Input Rate/Totalizer Instruction Manual 37 Selecting Input Type (Input) Seven input types may be set. See Rate Input specifications on pa
PD6830 Pulse Input Rate/Totalizer Instruction Manual 38
PD6830 Pulse Input Rate/Totalizer Instruction Manual 39 Entering the K-Factor (Factr) The meter may be scaled using the K-factor, or conversion facto
PD6830 Pulse Input Rate/Totalizer Instruction Manual 4 Table of Contents INTRODUCTION ----------------------------------------------------------------
PD6830 Pulse Input Rate/Totalizer Instruction Manual 40 K-Factor Value (factr) Enter the K-factor value. This value is entered in Pulses/Unit as defin
PD6830 Pulse Input Rate/Totalizer Instruction Manual 41 The following units may be selected as the base units for rate, total, and grand total. Time
PD6830 Pulse Input Rate/Totalizer Instruction Manual 42 Setting the Time Base (tbase) The meter calculates rate based on rate time base and rate displ
PD6830 Pulse Input Rate/Totalizer Instruction Manual 43 Setting the Rate Display Units (rateU) Rate is displayed in terms of a unit of volume, and a t
PD6830 Pulse Input Rate/Totalizer Instruction Manual 44 Total Units (tot U) This menu is used to select the display units for the total. The base unit
PD6830 Pulse Input Rate/Totalizer Instruction Manual 45 Grand Total Units (GtotU) This menu is used to select the display units for the grand total. T
PD6830 Pulse Input Rate/Totalizer Instruction Manual 46 Automatic Unit Conversions When switching from any standard unit of rate, total, or grand tota
PD6830 Pulse Input Rate/Totalizer Instruction Manual 47 Rate Conversion Factor is used to convert to a custom unit of rate display. For example, to di
PD6830 Pulse Input Rate/Totalizer Instruction Manual 48 Setting the Decimal Point (dec.PT) Rate decimal point may be set with up to four decimal place
PD6830 Pulse Input Rate/Totalizer Instruction Manual 49 Configuring the Display (Dsply) The top and bottom displays can be independently programmed to
PD6830 Pulse Input Rate/Totalizer Instruction Manual 5 Total Units (tot U) ------------------------------------------------------------------------- 4
PD6830 Pulse Input Rate/Totalizer Instruction Manual 50 Bottom Display (bOtm) The bottom display can be programmed to display the following informatio
PD6830 Pulse Input Rate/Totalizer Instruction Manual 51 Custom Tag (TAG) When the bottom display selected includes a custom tag, a User menu will then
PD6830 Pulse Input Rate/Totalizer Instruction Manual 52 Setting the Toggle Time (TIME) If the bottom display is programmed to toggle (TOGLE), the mete
PD6830 Pulse Input Rate/Totalizer Instruction Manual 53 Advanced Features Menu To simplify the setup process, functions not needed for most applicatio
PD6830 Pulse Input Rate/Totalizer Instruction Manual 54 Advanced menus A OUT displayed only for meters with the analog output option, COMM displaye
PD6830 Pulse Input Rate/Totalizer Instruction Manual 55 Advanced Features Menu & Display Messages The following table shows the Advanced features
PD6830 Pulse Input Rate/Totalizer Instruction Manual 56 Display Parameter Action/Setting OUt 1 Output 1 Output 1 value Dsp 2 Display 2 Output display
PD6830 Pulse Input Rate/Totalizer Instruction Manual 57 Display Parameter Action/Setting T DELAY Time delay Automatic reset time delay time Total Res
PD6830 Pulse Input Rate/Totalizer Instruction Manual 58 Display Parameter Action/Setting LOGTIME Log time Set daily data log times LOG 1 Log 1 Set fi
PD6830 Pulse Input Rate/Totalizer Instruction Manual 59 Open Collector Outputs (OUTPUT) The meter is equipped with two NPN open collector outputs that
PD6830 Pulse Input Rate/Totalizer Instruction Manual 6 Wakeup the Meter (WAKEUP?) ----------------------------------------------------------- 87OPERA
PD6830 Pulse Input Rate/Totalizer Instruction Manual 60 Output 1 and 2 Setup (OUT 1, OUT 2) The function of open collector output 1 and 2 is configure
PD6830 Pulse Input Rate/Totalizer Instruction Manual 61 Total & Grand Total Pulse Output (Total, Grtot) A total and grand total based pulse output
PD6830 Pulse Input Rate/Totalizer Instruction Manual 62 Alarm Output (alrm) Alarm outputs may be assigned to rate, total, or grand total; or be forced
PD6830 Pulse Input Rate/Totalizer Instruction Manual 63 If automatic total/grand total reset is enabled, the output will generate an alarm for a perio
PD6830 Pulse Input Rate/Totalizer Instruction Manual 64 Scaling the 4-20 mA Analog Output (Aout) The Analog Output menu is used to program the 4-20 m
PD6830 Pulse Input Rate/Totalizer Instruction Manual 65 Gate Function (GATE) The gate function is used for displaying slow pulse rates. Using the prog
PD6830 Pulse Input Rate/Totalizer Instruction Manual 66 Scaling & Calibration (SCALCAL) It is very important to read the following information, b
PD6830 Pulse Input Rate/Totalizer Instruction Manual 67 Scaling the Meter (SCale) The pulse input can be scaled to display the process variable in eng
PD6830 Pulse Input Rate/Totalizer Instruction Manual 68 Multi-Point Linearization (nopts) Up to 32 linearization points can be selected under the nopt
PD6830 Pulse Input Rate/Totalizer Instruction Manual 69 Calibrating the Meter (CaL) To scale the meter without a signal source refer to Entering the K
PD6830 Pulse Input Rate/Totalizer Instruction Manual 7 SPECIFICATIONS Except where noted all specifications apply to operation at +25°C. General DISPL
PD6830 Pulse Input Rate/Totalizer Instruction Manual 70 The multi-point linearization feature (nopts) can be used to linearize the display for non-lin
PD6830 Pulse Input Rate/Totalizer Instruction Manual 71 Error Message (Error) An error message indicates that the calibration or scaling process was
PD6830 Pulse Input Rate/Totalizer Instruction Manual 72 Manual or Automatic Total Reset Function (t rST) For manual reset, select T RESET t rst ma
PD6830 Pulse Input Rate/Totalizer Instruction Manual 73 Manual or Automatic Grand Total Reset Function (GtrST) For manual reset, select T RESET Gtrs
PD6830 Pulse Input Rate/Totalizer Instruction Manual 74 Setting Up Passwords (PASSWRD) The Password menu is used to program a five-digit password to p
PD6830 Pulse Input Rate/Totalizer Instruction Manual 75 Resetting Total & Grand Total on a Password Protected Meter If the meter is password prote
PD6830 Pulse Input Rate/Totalizer Instruction Manual 76 To configure the meter for non-resettable grand total mode, enter the non-resettable grand to
PD6830 Pulse Input Rate/Totalizer Instruction Manual 77 Custom (CUSTOM) The Custom menu is used to modify the initial programming menus that appear i
PD6830 Pulse Input Rate/Totalizer Instruction Manual 78 Custom Menu Parameters Display Parameter/Menu Action NONE None Set no menu position display I
PD6830 Pulse Input Rate/Totalizer Instruction Manual 79 LOGTIME Log Time Set daily data log times INTERVL Interval Set interval log times LOGVIEW Log
PD6830 Pulse Input Rate/Totalizer Instruction Manual 8 PASSWORD MENU OPTIONS Three programmable password selections can be used for the following: res
PD6830 Pulse Input Rate/Totalizer Instruction Manual 80 Set Real Time Clock (SETTIME) The real time clock is used to trigger data log events, and is
PD6830 Pulse Input Rate/Totalizer Instruction Manual 81 Data Log Setup (DATALOG) The Data Log menu is used to setup and enable the data log functions.
PD6830 Pulse Input Rate/Totalizer Instruction Manual 82 Log Time Setup (LOGTIME) The Log Time menu contains four log points (LOG 1 to LOG 4). Each log
PD6830 Pulse Input Rate/Totalizer Instruction Manual 83 View Data Log (LOGVIEW) The Log View menu allows on-screen browsing of the data log points sto
PD6830 Pulse Input Rate/Totalizer Instruction Manual 84 Backup & Restore (BACKUP) The features are used to save and restore programmed settings.
PD6830 Pulse Input Rate/Totalizer Instruction Manual 85 Battery Power Symbol Alert (BAT SYM) The Battery Power Symbol Alert menu is used to enable or
PD6830 Pulse Input Rate/Totalizer Instruction Manual 86 Serial Communications (COMM) The Communications menu is used to setup serial communications pa
PD6830 Pulse Input Rate/Totalizer Instruction Manual 87 Standby Mode (STANDBY) Standby mode is available on battery powered and battery backup models
PD6830 Pulse Input Rate/Totalizer Instruction Manual 88 OPERATION Front Panel Buttons Operation Symbol Description Hold the Menu SafeTouch® button
PD6830 Pulse Input Rate/Totalizer Instruction Manual 89 The following SafeTouch button information is reprinted from SafeTouch Button Operation on pa
PD6830 Pulse Input Rate/Totalizer Instruction Manual 9 ISOLATION All Models: 500 V opto-isolated input-to-power/output with isolated input enabled P
PD6830 Pulse Input Rate/Totalizer Instruction Manual 90 SafeTouch® Button Tips and Troubleshooting The SafeTouch Buttons are designed to filter normal
PD6830 Pulse Input Rate/Totalizer Instruction Manual 91 Grand Total Reading (GrTOTAL) The grand total is a separate total that is not reset when the t
PD6830 Pulse Input Rate/Totalizer Instruction Manual 92 Resetting the Total (RESET TOTAL?) If manual Total Reset is enabled in the Program menu, the t
PD6830 Pulse Input Rate/Totalizer Instruction Manual 93 Factory Defaults & User Settings The following table shows the factory setting for most of
PD6830 Pulse Input Rate/Totalizer Instruction Manual 94 Parameter Display Default Setting User SettingScale Enable SCALE No – Use K-Factor Scale/
PD6830 Pulse Input Rate/Totalizer Instruction Manual 95 TROUBLESHOOTING The rugged design and the user-friendly interface of the meter should make it
PD6830 Pulse Input Rate/Totalizer Instruction Manual 96 MOUNTING DIMENSIONS All units: inches [mm] Figure 16. Enclosure Dimensions – Front View
PD6830 Pulse Input Rate/Totalizer Instruction Manual 97 Figure 17. Enclosure Dimensions – Side Cross Section View 3.35 [85.0]4.15 [105.5]3.22 [81.
PD6830 Pulse Input Rate/Totalizer Instruction Manual 98 QUICK USER INTERFACE REFERENCE Pushbutton Function Menu Go to Programming mode, back out one